8 Troubleshooting and Maintenance
E3NW-ECT EtherCAT Digital Sensor Communication Unit Operation Manual (E429)
8-1 T
ro
u
b
lesho
o
ting
8
8-1-
4 Sysmac Err
or S
tatus Codes
Event name
Number of Sensors Over at Distributed Sensor Unit
Event code
247D0000 hex
Meaning
Too many Sensors are connected at Distributed Sensor Unit.
Source
EtherCAT Master Function Module
Source details
Slave
Detection
timing
Continuously
Error attributes
Level
Minor fault
Recovery
Error reset (after
automatic slave
recovery)
Log category
System
Effects
User program
Continues.
Operation
I/O communications and message communications are
not possible for the Sensors with relevant Distributed Sen-
sor Unit.
Indicators
EtherCAT NET RUN
EtherCAT NET ERR
EtherCAT LINK/ACT
---
---
---
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
More than the maximum number of
Sensors are connected at Distributed
Sensor Unit.
Reduce the number of Sensors at rel-
evant Distributed Sensor Unit to less
than the maximum number of Sen-
sors at Distributed Sensor Unit.
Do not connect more than the maxi-
mum number of Sensors at Distrib-
uted Sensor Unit.
Attached
information
None
Precautions/
Remarks
None
Event name
Dummy Sensors Setting Error
Event code
34F80000 hex
Meaning
Too many Dummy Units are set.
Source
EtherCAT Master Function Module
Source details
Slave
Detection
timing
When establish-
ing communica-
tions
Error attributes
Level
Minor fault
Recovery
Errors reset
Log category
System
Effects
User program
Continues.
Operation
Not affected.
Indicators
EtherCAT NET RUN
EtherCAT NET ERR
EtherCAT LINK/ACT
---
---
---
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
There are too many Dummy Units set,
so some Sensors are not assigned
logical unit numbers.
Reduce the number of Dummy Units
that is set in the dummy function set-
tings so that logical unit numbers can
be assigned to all connected Sen-
sors, and then change the Sensors
from the Init state to Pre-operational
state or restart the Sensors.
Set Dummy Units so that logical unit
numbers can be assigned to all Sen-
sor Amplifiers that are connected.
Attached
information
None
Precautions/
Remarks
None