![background image](http://html1.mh-extra.com/html/omron/e3nc/e3nc_operation-manual_741093056.webp)
5 EtherCAT Communications
5 - 10
E3NW-ECT EtherCAT Digital Sensor Communication Unit Operation Manual (E429)
5-5
Service Data Object (SDO)
E3NW-ECT EtherCAT Sensor Communication Units support the SDO communications.
The EtherCAT Master Unit is able to make parameter settings and monitor status by reading and writing
data from and to entries in object dictionaries via the SDO communications.
The table below shows abort codes of SDO communications errors.
The following table gives the abort codes for when sending commands to a Sensor Amplifier Unit fails.
5-5-1
Overview
5-5-2
Abort Codes
Code
Meaning
05030000 hex
Toggle bit not changed
05040000 hex
SDO protocol timeout
05040001 hex
Client/Server command specifier not valid or unknown
05040005 hex
Out of memory
06010000 hex
Unsupported access to an object
06010001 hex
Attempt to read a write only object
06010002 hex
Attempt to write to a read only object
06020000 hex
The object does not exist in the object directory.
06040041 hex
The object cannot be mapped into the PDO.
06040042 hex
The number and length of the objects to be mapped would exceed the PDO length.
06040043 hex
General parameter incompatibility reason
06040047 hex
General internal incompatibility in the device.
06060000 hex
Access failed due to a hardware error.
06070010 hex
Data type does not match, length of service parameter does not match.
06070012 hex
Data type does not match, length of service parameter too high.
06070013 hex
Data type does not match, length of service parameter too low.
06090011 hex
Sub-index does not exist.
06090030 hex
Value range of parameter exceeded (only for write access)
06090031 hex
Value of parameter written too high
06090032 hex
Value of parameter written too low
06090036 hex
Maximum value is less than minimum value.
08000000 hex
General error
08000020 hex
Data cannot be transferred or stored to the application.
08000021 hex
Data cannot be transferred or stored to the application because of local control.
08000022 hex
Data cannot be transferred or stored to the application because of the present device
state.
08000023 hex
Object dictionary dynamic generation fails or no object dictionary is present.
Value
Meaning
08000021 hex
An unsupported command was sent or the Sensor Amplifier Unit is in a condition under
which the command cannot be accepted. Check the command.
06090030 hex
A parameter value is out of range. Check the setting range of the parameter.
08000020 hex
A communications error or other error occurred. Implement retry processing.