9
CPM2C-S Features and Functions
Section 1-1
Note
1.
This input is shared by the high-speed counter and synchronized pulse
control functions.
2.
This output is shared by the pulse output and synchronized pulse control
functions.
Pulse outputs
•
2 outputs:
Single-phase pulse output without acceleration/deceleration (See note 2.)
10 Hz to 10 kHz
•
2 outputs:
Variable duty ratio pulse output (See note 2.)
0.1 to 999.9 Hz, duty ratio 0 to 100%
•
1 output:
Pulse output with trapezoidal acceleration/deceleration (See note 2.)
Pulse plus direction output, up/down pulse output, 10 Hz to 10 kHz
Synchronized pulse
control
1 point, see notes 1 and 2.
Input frequency range: 10 to 500 Hz, 20 Hz to 1 kHz, or 300 Hz to 20 kHz
Output frequency range: 10 Hz to 10 kHz
Quick-response input
2 inputs in CPU Units with 10 I/O points, 4 inputs in CPU Units with 20 I/O points
Minimum input signal width: 50
µ
s
Input time constant
Determines the input time constant for all inputs. (Settings: 1, 2, 3, 5, 10, 20, 40, or 80 ms)
Calendar/Clock
Shows the current year, month, day of the week, day of the month, hour, minute, and second.
Expansion Unit functions
Analog I/O functions using CPM2C-MAD11 Analog I/O Unit
•
Two analog inputs: Input range of 0 to 5 V, 1 to 5 V, 0 to 10 V, –10 to 10 V, 0 to 20 mA,
or 4 to 20 mA
•
One analog output: Output range of 1 to 5 V, 0 to 10 V, –10 to 10 V, 0 to 20 mA,
or 4 to 20 mA
Temperature sensing functions using CPM2C-TS001/101 Temperature Sensor Unit
•
Thermocouple input (measurement range): K (
−
200 to 1,300
°
C)
K (0.0 to 500.0
°
C)
J (–100 to 850
°
C)
J (0.0 to 400.0
°
C)
•
Platinum resistance thermometer (measurement range): Pt100 (–200.0 to 650.0
°
C)
JPt100 (–200.0 to 650.0
°
C)
CompoBus/S Slave functions using CPM2C-SRT21 CompoBus/S I/O Link Unit
Data exchange with the Master Unit via 8 inputs and 8 outputs.
Main function
Variations/Details
Summary of Contents for CPM2C-S100C
Page 2: ......
Page 3: ...CPM2C S Programmable Controller Operation Manual Revised September 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 10: ......
Page 14: ...xiv ...
Page 180: ...158 One to one PC Link I O Response Time Section 7 4 ...
Page 222: ...200 Programming Example Section 8 3 ...
Page 250: ......
Page 256: ......
Page 258: ......
Page 260: ...238 Support Software Appendix C ...
Page 268: ......