Remote I/O Communications
Section 5-2
5-2-2
I/O Allocation
In the CPM2C-S, CompoBus/S input words IR 020 to IR 027 and CompoBus/
S output words IR 030 to IR 037 are allocated for the CompoBus/S Terminal’s
I/O. The CompoBus/S Terminal’s I/O (IN0 to IN15 and OUT0 to OUT15) are
allocated as indicated in the following table.
IN0 to IN15 are the node addresses for the Input Terminals and OUT0 to
OUT15 are the node addresses for the Output Terminals.
Note
1.
When the maximum number of CompoBus/S nodes is set to 16, IN8 to
IN15 and OUT8 to OUT15 can be used as work bits.
2.
CompoBus/S Terminals with less than 8 points are allocated bit addresses
from either 0 or 8, filling up from the lowest available word.
3.
CompoBus/S Terminals with 16 points can be set for only even number ad-
dresses.
Bit-chain Terminal
Not available
SRT1-B1T
Environment Resistive Terminals
SRT2-ID04CL
SRT2-ID04CL-1
SRT2-ID08
SRT2-ID08CL-1
SRT2-OD04CL
SRT2-OD04CL-1
SRT2-OD08CL
SRT2-OD08CL-1
Not available
Name
SRT2-series
SRT1-series
Word
Relay numbers
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Input
IR 020
IN1
IN0
IR 021
IN3
IN2
IR 022
IN5
IN4
IR 023
IN7
IN6
IR 024
IN9
IN8
IR 025
IN11
IN10
IR 026
IN13
IN12
IR 027
IN15
IN14
Output
IR 030
OUT1
OUT0
IR 031
OUT3
OUT2
IR 032
OUT5
OUT4
IR 033
OUT7
OUT6
IR 034
OUT9
OUT8
IR 035
OUT11
OUT10
IR 036
OUT13
OUT12
IR 037
OUT15
OUT14
Summary of Contents for CPM2C-S100C
Page 2: ......
Page 3: ...CPM2C S Programmable Controller Operation Manual Revised September 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 10: ......
Page 14: ...xiv ...
Page 180: ...158 One to one PC Link I O Response Time Section 7 4 ...
Page 222: ...200 Programming Example Section 8 3 ...
Page 250: ......
Page 256: ......
Page 258: ......
Page 260: ...238 Support Software Appendix C ...
Page 268: ......