133
Explicit Message Communications
Section 6-3
C200HW Master in a CS Series PC: Reading Data with IOWR
(––)
This example shows the instruction operands and results of the IOWR com-
mand when 20 words of data are read from IR 010 to IR 029 in a Slave, and
written to response words from DM 2000 to the end in a Master mounted in a
CS-series PC.
Refer to the
DeviceNet Masters Unit Operation Manual
(W379) for details on
explicit messages, and refer to the
SYSMAC CS/CJ Series Communications
Commands Reference Manual
(W342) for details on IOWR(––).
Example Network
Conditions
Master’s node number:
63
Slave’s node number:
2
IOWR(––) Operand Details
• Control Code
• Command Words
• Destination Information
• Response Words (The results are stored as follows.)
[IOWR
C
S
W]
Word
Contents
(Hex)
Function
C
3F FE
Master’s node number = 3F (Hex) specifies 63
Master’s unit address = FE (Hex) specifies the local Unit
Word
Contents
(Hex)
Function
S
82 07
Specifies starting response word = DM 2000
82 (Hex) specifies the DM area
07D0 (Hex) specifies address 2000
(Refer to the
CS Series Operation Manual
(W339) for details.)
S+1
D0 00
S+2
00 64
Response monitoring time = 10.0 seconds
S+3
00 0B
Number of bytes of command data beginning with word S+4 =
0B (Hex) specifies 11 bytes
S+4
28 01
EXPLICIT MESSAGE SEND command code = 2801 (Hex)
S+5
02 1C
Slave node number = 02 (Hex)
READ BYTE DATA command service code = 1C (Hex)
S+6
00 2F
Class ID = 002F (Hex)
S+7
00 01
Instance ID = 0001 (Hex) specifies data area
S+8
0A 00
Starting read address = 000A (Hex) specifies IR 010
Address L = 0A (Hex); Address H = 00 (Hex)
S+9
28 00
Number of bytes of data to read = 28 (Hex) specifies 40 bytes
Word
Contents
(Hex)
Function
W
00 00
Master Unit’s unit number = 00 (Hex) specifies 0
W+1
00 10
Number of words of command data beginning with word S+0 =
10 (BCD) specifies 10 words
Word
Contents
(Hex)
Function
DM 2000
28 01
EXPLICIT MESSAGE SEND command code = 2801 (Hex)
DM 2001
00 00
Normal completion code = 0000 (Hex)
DM 2002
00 2A
Number of bytes received = 2A (Hex) indicates 42 bytes
(This is the number of bytes from D+3 to the end.)
DM 2003
02 9C
Slave’s node number = 02 (Hex)
READ BYTE DATA response service code = 9C (Hex)
DM 2004
HH LL
These words contain the data to be read from Slave
words IR 010 to IR 029.
When the READ BYTE DATA command is executed from an
OMRON Master, the bytes are written to the Master in the
same order (HH LL) in which they appear in the Slave.
Summary of Contents for CPM2C-S100C
Page 2: ......
Page 3: ...CPM2C S Programmable Controller Operation Manual Revised September 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 10: ......
Page 14: ...xiv ...
Page 180: ...158 One to one PC Link I O Response Time Section 7 4 ...
Page 222: ...200 Programming Example Section 8 3 ...
Page 250: ......
Page 256: ......
Page 258: ......
Page 260: ...238 Support Software Appendix C ...
Page 268: ......