199
Programming Example
Section 8-3
If errors are displayed, edit the program to correct the errors and check the
program again. Continue checking the program until all errors have been cor-
rected.
8-3-5
Test Run in MONITOR Mode
Switch the CPM2C-S in MONITOR mode and check the operation of the pro-
gram.
1,2,3...
1.
Set the Programming Console’s mode switch to MONITOR mode.
2.
Press the CLR Key to bring up the initial display.
3.
Force-set the start input bit (IR 00000) from the Programming Console to
start the program.
The cursor in the lower left corner of the display indicates that the force set
is in progress. The bit will remain ON as long as the Set Key is held down.
4.
The output indicator for output IR 01000 will flash ten times if the program
is operating correctly. The indicator should go OFF after ten one-second
flashes.
There is a mistake in the program if the output indicator doesn’t flash. In
this case, check the program and force set/reset bits to check operation.
RUN
MONITOR
PROGRAM
<MONITOR>
BZ
CLR
LD
LD
00000
MONTR
^ OFF
SET
ON
Summary of Contents for CPM2C-S100C
Page 2: ......
Page 3: ...CPM2C S Programmable Controller Operation Manual Revised September 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 10: ......
Page 14: ...xiv ...
Page 180: ...158 One to one PC Link I O Response Time Section 7 4 ...
Page 222: ...200 Programming Example Section 8 3 ...
Page 250: ......
Page 256: ......
Page 258: ......
Page 260: ...238 Support Software Appendix C ...
Page 268: ......