61
Wiring and Connections
Section 3-4
Floor Ducts
Leave at least 200 mm between the wiring and the top of the duct, as shown
in the following diagram.
Conduits
Separate the CPM2C-S I/O lines, power and control lines, and power cables,
as shown in the following diagram.
3-4-2
Power Supply Wiring
The following procedure explains how to connect the CPU Unit to the AC
Power Supply Unit (CPM2C-PA201) with the power supply connector
(included) to provide a 24-VDC power supply.
200 mm min.
Metal plate (iron)
CPM2C-S
I/O lines
Control cables and
CPM2C-S power
lines
Power
cables
CompoBus/S and DeviceNet
communications cables
CPM2C-S
I/O lines
Control cables
and CPM2C-S
power lines
Power
cables
CompoBus/S and
DeviceNet communications
cables
Power supply connector
(included with the Unit)