Maintenance Inspections
Section 9-6
9-6
Maintenance Inspections
In order for your SYSMAC system to operate in optimum condition, be sure to
carry out daily or periodical inspections.
Inspection Items
The main system components of a SYSMAC system are semiconductors, and
it contains few components with limited lifetimes. Poor environmental condi-
tions, however, can lead to deterioration of the electrical components, making
regular maintenance necessary.
The standard period for maintenance checks is 6 months to 1 year, but more
frequent checks are required if the PC is operated in more demanding condi-
tions.
If the criteria are not met, adjust to within the specified ranges.
Note
Power supply voltage range:
Required Tools
Standard Tools (Required)
• Screwdrivers (Phillips and flat-blade)
• Voltage tester or digital voltage meter
• Industrial alcohol and a cotton cloth
Measurement Devices (May be Needed)
• Synchroscope
• Cathode-ray oscilloscope
• Thermometer, hygrometer
Note
Do not attempt to disassemble, repair, or modify the PC in any way.
Inspection items
Details
Criteria
Remarks
Power supply
Determine whether the voltage fluctuation
at the power supply terminals is within
specifications.
Within the voltage variation
range (see note)
Tester
Environmental con-
ditions
Is the ambient temperature inside the panel
appropriate?
0 to 55
°
C
Thermometer
Is the ambient humidity inside the panel
appropriate?
10% to 90% RH with no con-
densation
Hygrometer
Has dirt or dust collected?
None
Visual inspection
I/O power supply
Is the voltage fluctuation measured at the I/
O terminals within the standard range?
Each I/O terminal must con-
form to the specifications
Tester
Installation status
Are all units securely installed?
Nothing is loose
Phillips screwdriver
Are all connection cables and connectors
inserted completely and locked?
Nothing is loose
Visual inspection
Are any of the external wiring screws loose? Nothing is loose
Phillips screwdriver
Are any of the external wiring cables
frayed?
No external abnormalities
Visual inspection
Product service life
Contact output relay
Electrical:
Resistance load:
150,000 operations
Inductive load:
100,000 operations
Mechanical:
20,000,000 operations
---
Battery (CPM2C-BAT01)
2 years at 25
°
C
---
Power supply
Allowable voltage fluctuation range
100 to 240 VAC (CPM2C-PA201 only)
85 to 264 VAC
24 VDC
20.4 to 26.4 VDC
Summary of Contents for CPM2C-S100C
Page 2: ......
Page 3: ...CPM2C S Programmable Controller Operation Manual Revised September 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 10: ......
Page 14: ...xiv ...
Page 180: ...158 One to one PC Link I O Response Time Section 7 4 ...
Page 222: ...200 Programming Example Section 8 3 ...
Page 250: ......
Page 256: ......
Page 258: ......
Page 260: ...238 Support Software Appendix C ...
Page 268: ......