Specifications and Configurations
Section 1-2
Functions Supported by CS/CJ-series Controller Link Units
Note
1.
A maximum of 32 nodes can be set without using a Repeater Unit (CS1W-
RPT0
@
).
2.
A network can contain both new and old models. In that case, the system
must be configured using the specifications for the old models. The num-
ber of data link send and receive words, however, can be set separately for
old and new models with up to the maximum number of words set for each.
Use the CX-Net in CX-Programmer version 5.0 or higher to set a data link
area in which the number of send and receive words exceeds 12,000 words.
CX-Integrator version 3.2 or higher can be used to change data link alloca-
tions while manually set data links are active.
Up to eight CS/CJ-series Controller Link Units with unit version 1.2 or later
can be connected to a single CPU Unit. When connecting multiple Controller
Link Units to the CPU Unit, consider the current consumption of the CPU Unit
and each CPU Bus Unit before selecting the Power Supply Unit. For details on
Controller Link Unit current consumption, refer to
on page 18. For details on current consumption of each Unit, refer
to the operation manual of the PLC that is being used.
The following table provides an example of current consumption.
Example: Using the C200HW-PA204 Power Supply Unit supplying a maxi-
mum current of 4.6 A (5 V) and maximum power of 30 W.
Model
CS1W-CLK23
CJ1W-CLK23
CS1W-CLK21-V1
CJ1W-CLK21-V1
Item
Ver. 1.2
Pre-Ver. 1.2
Maximum number of send/receive data link
words (data link areas for sending/receiving
that are created for a single node in a single
CPU Unit)
20,000 words max.
12,000 words max.
Number of send words per node (total of area
1 and area 2)
4,000 words max.
(optional setting only)
1,000 words max.
Data Link Area
Area 1 and Area 2 can be allocated in the same
area.
Area 1 and Area 2 can-
not be allocated in the
same area.
Maximum number of Units connected to a sin-
gle CPU Unit
8 Units
4 Units
Automatic data link setting
Select from equality layout or 1:N allocations (common type, 1:1 type,
chain type)
Changing data link allocations during active
data links
Supported. (Data link tables can be changed during active data links.)
Maximum number of nodes that can be con-
nected
62 Units (See note 1.).
Mixed use
Supported (See note 2.)
Name
Model
Current consumption
per Unit (A)
Number of
Units
Current consumption
(A)
CPU Backplane (8 slots)
CS1W-BC083
0.11 A
1
0.11 A
CPU Unit
CS1H-CPU67H
0.82 A
1
0.82 A
Controller Link Unit (Optical)
CS1W-CLK21-V1
0.33 A
8
2.64 A
Total
3.57 (power consump-
tion: 17.85 W)
Summary of Contents for C200HW-CLK21
Page 3: ...iv ...
Page 9: ...x ...
Page 12: ...xiii TABLE OF CONTENTS Index 367 Revision History 373 ...
Page 13: ...xiv ...
Page 19: ...xx ...
Page 57: ...32 Application Precautions Section 1 5 Example CX Programmer Response Timeout Setting ...
Page 69: ...44 Message Service Procedure Section 2 2 ...
Page 111: ...86 Constructing Networks with Repeater Units Section 3 4 ...
Page 154: ...129 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 261: ...236 Response Codes Section 6 7 ...
Page 297: ...272 Message Delay Times Section 8 4 ...
Page 353: ...328 Handling Precautions Section 9 6 ...
Page 364: ...339 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 365: ...340 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 369: ...344 Standard Models Appendix A ...
Page 391: ...366 Using the Relay Terminal Block Appendix C ...
Page 397: ...372 Index ...
Page 401: ...376 Revision History ...