280
Troubleshooting Using Indicators
Section 9-1
The data link status
is showing statuses
of 32 nodes only.
The data link status
storage area is set to
default settings, and
the data link status
storage format speci-
fication in the DM
Parameters Area is
set to the 8-bit for-
mat.
The default area for storing data link
status is the Special I/O Unit Area. The
data for only node addresses 1 to 32 is
reflected when the data link status stor-
age format specification is set to 8 bits.
The polling node is a
C200HW-CLK21,
CQM1H-CLK21,
CVM1-CLK21,
CS1W-CLK21, or
CJ1W-CLK21.
The Units that can be used to configure
a network of a network that uses a
node address higher than 32 are the
CS1W-CLK21-V1, CS1W-CLK23,
CJ1W-CLK21-V1, and CJ1W-CLK23
only. Either configure the network using
compatible Units and Boards, or split
the network into two separate net-
works.
The polling node is a
CS1W-CLK21-V1,
CS1W-CLK23,
CJ1W-CLK21-V1, or
CJ1W-CLK23
The Wired Network 62 Node Enable Bit
in the DM Parameters Area of the poll-
ing node (CS1W-CLK21-V1, CS1W-
CLK23, CJ1W-CLK21-V1, or CJ1W-
CLK23 with INS indicator ON) is OFF.
Turn ON the Wired Network 62 Node
Enable Bit, then turn the power supply
OFF and ON again.
Error occurs when
transferring data link
tables.
The data link table
being transferred is
for a C200HW-
CLK21, CQM1H-
CLK21, CVM1-
CLK21, CS1W-
CLK21, or CJ1W-
CLK21.
The Units that can be used to configure
a network of a network that uses a
node address higher than 32 are the
CS1W-CLK21-V1, CS1W-CLK23,
CJ1W-CLK21-V1, and CJ1W-CLK23
only. Either configure the network using
compatible Units and Boards, or split
the network into two separate net-
works.
The data link status
is showing statuses
of 32 nodes only.
The polling node is a
C200HW-CLK21,
CQM1H-CLK21,
CVM1-CLK21,
CS1W-CLK21, or
CJ1W-CLK21.
The polling node is a
CS1W-CLK21-V1,
CS1W-CLK23,
CJ1W-CLK21-V1, or
CJ1W-CLK23.
The Wired Network 62 Node Enable Bit
in the DM Parameters Area of the poll-
ing node (CS1W-CLK21-V1, CS1W-
CLK23, CJ1W-CLK21-V1, or CJ1W-
CLK23 with INS indicator ON) is OFF.
Turn ON the Wired Network 62 Node
Enable Bit, then turn the power supply
OFF and ON again.
Problem
Status
Cause and remedy
Summary of Contents for C200HW-CLK21
Page 3: ...iv ...
Page 9: ...x ...
Page 12: ...xiii TABLE OF CONTENTS Index 367 Revision History 373 ...
Page 13: ...xiv ...
Page 19: ...xx ...
Page 57: ...32 Application Precautions Section 1 5 Example CX Programmer Response Timeout Setting ...
Page 69: ...44 Message Service Procedure Section 2 2 ...
Page 111: ...86 Constructing Networks with Repeater Units Section 3 4 ...
Page 154: ...129 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 261: ...236 Response Codes Section 6 7 ...
Page 297: ...272 Message Delay Times Section 8 4 ...
Page 353: ...328 Handling Precautions Section 9 6 ...
Page 364: ...339 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 365: ...340 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 369: ...344 Standard Models Appendix A ...
Page 391: ...366 Using the Relay Terminal Block Appendix C ...
Page 397: ...372 Index ...
Page 401: ...376 Revision History ...