231
Response Codes
Section 6-7
01: Local node error
01
Local node not part of Network
Add to Network.
02
Token time-out, node address too large Set the local node’s node address below
the maximum node address.
03
Number of transmit retries exceeded
Check communications with ECHOBACK
TEST. If the test fails, check network.
04
Maximum number of frames exceeded
Either check the execution of events in the
network and reduce the number of events
occurring in one cycle, or increase the max-
imum number of frames.
05
Node address setting error (range)
Correctly set the Controller Link BIOS /N
option. Make sure the node address is
within specified range and that there are no
node addresses that are set twice.
06
Node address duplication error
Make sure that there are no node
addresses that are set twice.
02: Destination node
error
01
Destination node not part of Network
Add to Network.
02
No node with the specified node
address
Check the destination node’s node address.
03
Third node not part of Network
Check the third node’s node address.
Broadcasting was specified.
Check the control data and specify only one
node as the third node.
04
Busy error, destination node busy
Increase the number of transmit retry
attempts or re-evaluate the system so that
the destination node is not so busy receiv-
ing data.
05
Response time-out, message packet
was corrupted by noise
Increase the number of transmit retry
attempts.
Response time-out, response watch-
dog timer interval too short
(If a large number of data links is used,
the response monitor time will be
shorter than the communications cycle
time.)
Increase the value for the response watch-
dog timer interval in the control data.
Frame lost in transmission
Check the error log and correct the process.
03: Communications con-
troller error
01
Error occurred in the communications
controller, ERC indicator is lit
Take corrective action, referring to commu-
nications controller errors and remedies
table at end of this section.
02
CPU Unit error occurred in the PLC at
the destination node
Clear the error in the CPU Unit (refer to the
PLC’s operation manuals).
03
A controller error has prevented a nor-
mal response from being returned.
Check network communications status and
reset the controller board. If the error still
exists, replace the controller board.
04
Unit address setting error
Make sure the Unit address is within the
specified range and that there are no node
addresses that are set twice.
04: Not executable
01
An undefined command has been
used.
Check the command code and be sure that
the Unit supports it.
02
Cannot process command because the
specified unit model or version is
wrong.
Check the unit model and version.
Main code
Sub-
code
Probable cause
Remedy
Summary of Contents for C200HW-CLK21
Page 3: ...iv ...
Page 9: ...x ...
Page 12: ...xiii TABLE OF CONTENTS Index 367 Revision History 373 ...
Page 13: ...xiv ...
Page 19: ...xx ...
Page 57: ...32 Application Precautions Section 1 5 Example CX Programmer Response Timeout Setting ...
Page 69: ...44 Message Service Procedure Section 2 2 ...
Page 111: ...86 Constructing Networks with Repeater Units Section 3 4 ...
Page 154: ...129 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 261: ...236 Response Codes Section 6 7 ...
Page 297: ...272 Message Delay Times Section 8 4 ...
Page 353: ...328 Handling Precautions Section 9 6 ...
Page 364: ...339 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 365: ...340 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 369: ...344 Standard Models Appendix A ...
Page 391: ...366 Using the Relay Terminal Block Appendix C ...
Page 397: ...372 Index ...
Page 401: ...376 Revision History ...