71
Wiring
Section 3-3
5.
Twist firmly the portion of the signal lines that are exposed.
6.
Apply vinyl tape or heat-shrinking tube to the end of the cover that was
peeled in step 1.
7.
Mount the crimp terminal onto the signal lines and the shield line.
Use M3 crimp terminals, as illustrated below.
8.
Connect the signal lines and the shield line to the terminal block using the
markings on the terminal block.
Note a)
You can change the length of the signal lines as shown in the fol-
lowing diagrams to make wiring a lot easier.
Apply vinyl tape or a
heat-shrinking tube.
6.2 mm max.
6.2 mm max.
Shield line
Communications cable
from the previous node
Communications cable
to the next node
Communications data
High signal
Communications data
Low signal
Approx. 30 mm
Approx. 50 mm
Approx. 40 mm
Summary of Contents for C200HW-CLK21
Page 3: ...iv ...
Page 9: ...x ...
Page 12: ...xiii TABLE OF CONTENTS Index 367 Revision History 373 ...
Page 13: ...xiv ...
Page 19: ...xx ...
Page 57: ...32 Application Precautions Section 1 5 Example CX Programmer Response Timeout Setting ...
Page 69: ...44 Message Service Procedure Section 2 2 ...
Page 111: ...86 Constructing Networks with Repeater Units Section 3 4 ...
Page 154: ...129 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 261: ...236 Response Codes Section 6 7 ...
Page 297: ...272 Message Delay Times Section 8 4 ...
Page 353: ...328 Handling Precautions Section 9 6 ...
Page 364: ...339 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 365: ...340 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 369: ...344 Standard Models Appendix A ...
Page 391: ...366 Using the Relay Terminal Block Appendix C ...
Page 397: ...372 Index ...
Page 401: ...376 Revision History ...