28
Basic Procedures
Section 1-4
• Connect the communications cables.
2.
Set the node address on the front rotary switches.
• 01 to 32
3.
Set the baud rate and operating level on the front DIP switch.
• 2 M, 1 M, or 500 Kbps
• Operating level 0 or operating level 1 (C200HX/HG/HE PLCs only)
4.
Set the terminating resistance on the sliding switch.
• ON or OFF (Only the end nodes are set to ON.)
5.
Connect power to all nodes.
6.
Connect the Programming Device to the PLC.
7.
Create I/O tables (not necessary for C200HX/HG/HE and CQM1H-
series PLCs and not necessary for CJ-series PLCs unless user-created
I/O tables have been specified).
8.
Register routing tables as required.
CVM1, CV-series, and CS/CJ-series PLCs
1,2,3...
1.
Perform mounting and wiring.
• Mount to the PLC.
• Connect the communications cables.
2.
Set the Unit number on the front rotary switches.
• 00 to 15 (0 to F: CS/CJ-series display is in hexadecimal)
3.
Set the node address on the front rotary switches.
• 01 to 32 (01 to 62) (See note a.)
4.
Set the baud rate and operating level on the front DIP switch.
• 2 M, 1 M, or 500 Kbps (wired systems only)
5.
Set the terminating resistance on the front slide switch.
• ON or OFF (Only the terminal node is set to ON.)
6.
Connect power to all nodes.
7.
Connect the Programming Device to the PLC.
8.
Create I/O tables (not necessary for C200HX/HG/HE and CQM1H-
series PLCs and not necessary for CJ-series PLCs unless user-created I/
O tables have been specified).
9. Set the Wired Network 62 Node Enable Bit in the DM Parameter Area soft-
ware switches. (See note b.)
• ON (62 nodes max.) or OFF (32 nodes max.)
10. Register routing tables.
Note a) Setting 62 nodes is possible only with the CS1W-CLK21-V1,
CS1W-CLK23, CJ1W-CLK21-V1, and CJ1W-CLK23.
The Wired
Network 62 Node Enable Bit in the DM Parameter Area software
switches must be set.
b) This setting is valid only with the CS1W-CLK21-V1, CS1W-
CLK23, CS1W-CLK21-V1, and CS1W-CLK23. Reset the power to
the PLC after setting.
Data Link Procedure
Set the data link mode in the data link parameters in the DM area of the star-
tup node to either automatic or manual data link creation using the Program-
ming Device.
Summary of Contents for C200HW-CLK21
Page 3: ...iv ...
Page 9: ...x ...
Page 12: ...xiii TABLE OF CONTENTS Index 367 Revision History 373 ...
Page 13: ...xiv ...
Page 19: ...xx ...
Page 57: ...32 Application Precautions Section 1 5 Example CX Programmer Response Timeout Setting ...
Page 69: ...44 Message Service Procedure Section 2 2 ...
Page 111: ...86 Constructing Networks with Repeater Units Section 3 4 ...
Page 154: ...129 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 261: ...236 Response Codes Section 6 7 ...
Page 297: ...272 Message Delay Times Section 8 4 ...
Page 353: ...328 Handling Precautions Section 9 6 ...
Page 364: ...339 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 365: ...340 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 369: ...344 Standard Models Appendix A ...
Page 391: ...366 Using the Relay Terminal Block Appendix C ...
Page 397: ...372 Index ...
Page 401: ...376 Revision History ...