99
CVM1 and CV-series Controller Link Units
Section 4-4
4-4
CVM1 and CV-series Controller Link Units
The following settings are required for a Controller Link Unit when used with a
CVM1 or CV-series PLC.
4-4-1
Overview
Unit Number
Node Addresses
Setting Baud Rates
Note
The factory default setting is in bold.
Always keep pins 3 and 4 set to OFF.
Terminating Resistance
Item
Switch
Page
Unit number
Unit number switch
Node address
Node address switch
Baud rate
Baud rate switch, pins 1 and 2
Terminating resistance
Terminating resistance switch
ON
CLK21
X10
1
X10
0
SW1
BD H
BD L
SHLD
RUN
ERC
M/A
LNK
TER SW
1
2
3
4
BAUD
RATE
BAUD RATE
0
0
INS
SD
M/A
LNK
RD
X10
0
NODE
NO.
X10
1
UNIT
NO.
X10
1
RSV
0
0
BIT2 BIT1
RATE
RSV
OFF OFF
2MBP
OFF ON
1MBP
ON
OFF
500KBP
NODE
NO.
X10
1
X10
0
1
2
3
4
RSV
BAUD
RATE
0
ON
3
2
14
X10
0
UNIT
NO.
X10
1
RSV
0
0
1
Setting range
Nodes
00 to 15 (default is 00)
All nodes in the Network
Setting range
Nodes
01 to 32 (default is 01)
All nodes in the Network
Switch
Baud rate
Maximum
transmis-
sion dis-
tance
Nodes
Pin 1
Pin 2
OFF
OFF
2 Mbps
500 m
Set same
rate for all
nodes in
Network.
ON
OFF
1 Mbps
800 m
OFF
ON
500 Kbps
1 km
ON
ON
Do not set.
Bottom switch
Terminating
resistance
Nodes
OFF
(factory default)
Not connected
All the nodes
Turn ON the terminating resis-
tance at the nodes at both
ends of the Network and turn it
OFF at all other nodes.
ON
Connected
Summary of Contents for C200HW-CLK21
Page 3: ...iv ...
Page 9: ...x ...
Page 12: ...xiii TABLE OF CONTENTS Index 367 Revision History 373 ...
Page 13: ...xiv ...
Page 19: ...xx ...
Page 57: ...32 Application Precautions Section 1 5 Example CX Programmer Response Timeout Setting ...
Page 69: ...44 Message Service Procedure Section 2 2 ...
Page 111: ...86 Constructing Networks with Repeater Units Section 3 4 ...
Page 154: ...129 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 261: ...236 Response Codes Section 6 7 ...
Page 297: ...272 Message Delay Times Section 8 4 ...
Page 353: ...328 Handling Precautions Section 9 6 ...
Page 364: ...339 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 365: ...340 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 369: ...344 Standard Models Appendix A ...
Page 391: ...366 Using the Relay Terminal Block Appendix C ...
Page 397: ...372 Index ...
Page 401: ...376 Revision History ...