35
Data Links Procedures
Section 2-1
6.
Set the data link mode.
Note a)
When using fewer than 33 nodes, make sure that the Wired Net-
work 62 Node Enable Bit if the DM Parameter Area software
switch is turned OFF to restrict the network to 32 nodes maximum.
To construct a network that uses a node address higher than 32,
all nodes must use the CS1W-CLK21-V1, CS1W-CLK23, CJ1W-
CLK21-V1, or CJ1W-CLK23.
b)
Only node addresses 1 through 32 can be used on networks for
which 62 nodes have not been enabled.
c)
Be sure that the data link mode in the data link parameters in the
DM Area is set to 00 when using manually set data links.
d)
When using the 8-bit storage format, make sure that the relevant
locations in the DM Parameter Area are set to 0. The storage for-
mat used by all models other than CS1W-CLK21-V1, CS1W-
CLK23, CJ1W-CLK21-V1, and CJ1W-CLK23 is fixed at 8-bit, re-
gardless of the setting.
7.
Register the data link tables by making the following settings for each
node.
Note
Offsets are used to control where data is placed within the receive
area.
Contents
Method
Nodes
Page
Enable 62 nodes for a
wired network.
Use Support Soft-
ware for the PLC or
the Programming
Console.
All nodes
Note: This setting
must be made to con-
struct a network that
uses a node address
higher than 32 (See
note a.)
Set data link mode to
manual.
Use Support Soft-
ware for the PLC or
the Programming
Console. (See note b.)
Data link startup node
only
The node that is used
to start the data links
is called the startup
node. It is necessary
to decide beforehand
which node will be the
startup node.
Set the data link status
storage format. (CS/
CJ Series only)
Use Support Soft-
ware for the PLC or
the Programming
Console.
Data link startup node
only (See note c.)
Contents
Method
Nodes
Page
First data link status word
Use the Controller
Link Support Soft-
ware or CX-Pro-
grammer.
All nodes within the
network
Delete from the data
link tables all nodes
that are not in a data
link.
Data link nodes
Area
1
First data link sta-
tus words
Numbers of data
link words
Data link offsets
Area
2
First data link sta-
tus words
Numbers of data
link words
Data link offsets
Summary of Contents for C200HW-CLK21
Page 3: ...iv ...
Page 9: ...x ...
Page 12: ...xiii TABLE OF CONTENTS Index 367 Revision History 373 ...
Page 13: ...xiv ...
Page 19: ...xx ...
Page 57: ...32 Application Precautions Section 1 5 Example CX Programmer Response Timeout Setting ...
Page 69: ...44 Message Service Procedure Section 2 2 ...
Page 111: ...86 Constructing Networks with Repeater Units Section 3 4 ...
Page 154: ...129 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 261: ...236 Response Codes Section 6 7 ...
Page 297: ...272 Message Delay Times Section 8 4 ...
Page 353: ...328 Handling Precautions Section 9 6 ...
Page 364: ...339 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 365: ...340 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 369: ...344 Standard Models Appendix A ...
Page 391: ...366 Using the Relay Terminal Block Appendix C ...
Page 397: ...372 Index ...
Page 401: ...376 Revision History ...