16
Specifications and Configurations
Section 1-2
CS1W-CLK21-V1, CS1W-CLK23, CJ1W-CLK21-V1, CJ1W-CLK23,
3G8F7-CLK21-V1, and 3G8F7-CLK23-E
2.
Using 62,000 data link words is possible with a configuration containing 62
nodes.
Communications Specifications when Using the CS1W-RPT01 Repeater Unit in a Wired
Network
Note
1.
Specifications within a segment are identical to the specifications of a
Wired Controller Link Network.
2.
Maximum transmission distance: Total length of cables in the longest path
connecting any two nodes.
3.
A maximum of 62 nodes is possible only when using CS1W-CLK21-V1,
CS1W-CLK23, CJ1W-CLK21-V1, CJ1W-CLK23, 3G8F7-CLK21-V, and
3G8F7-CLK23-E Units.
4.
Maximum number of Repeater stages: The maximum number of Repeater
Units that can be inserted into the path connecting any two nodes. For
wire-to-optical connection, two Repeater Units make up a single set, which
is counted as a single Repeater stage.
5.
The Repeater Units each have a unique node address. Up to 32 Units,
consisting of Controller Link Units and Repeater Units, can be connected
within a single segment.
Item
Within 1 segment
(See note 1.)
Entire network
Transmission path form
Multi-drop
Tree type (Connection of
segments with Repeaters)
Baud rate and maximum trans-
mission distance (See note 2.)
2 Mbps: 500 m
1 Mbps: 800 m
500 Kbps: 1 km
2 Mbps: 1.5 km
1 Mbps: 2.4 km
500 Kbps: 3.0 km
Maximum number of nodes
Total number of Control-
ler Link Units + Repeater
Units: 32 nodes (See
note 5.)
Controller Link Units/Sup-
port Boards (See note 3.):
62 nodes
Maximum number of Repeater
stages (See note 4.)
---
2 stages
Wire
Optical
fiber
cable
: Wire-to-wire Repeater Unit
: Range of a single segment
: Controller Link Unit/Support
Board
: Wire-to-optical Repeater Unit
(two Units used in a pair)
Note:
The Repeater Unit will be
counted in the number of
nodes for each segment that
it is connected to.
Summary of Contents for C200HW-CLK21
Page 3: ...iv ...
Page 9: ...x ...
Page 12: ...xiii TABLE OF CONTENTS Index 367 Revision History 373 ...
Page 13: ...xiv ...
Page 19: ...xx ...
Page 57: ...32 Application Precautions Section 1 5 Example CX Programmer Response Timeout Setting ...
Page 69: ...44 Message Service Procedure Section 2 2 ...
Page 111: ...86 Constructing Networks with Repeater Units Section 3 4 ...
Page 154: ...129 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 261: ...236 Response Codes Section 6 7 ...
Page 297: ...272 Message Delay Times Section 8 4 ...
Page 353: ...328 Handling Precautions Section 9 6 ...
Page 364: ...339 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 365: ...340 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 369: ...344 Standard Models Appendix A ...
Page 391: ...366 Using the Relay Terminal Block Appendix C ...
Page 397: ...372 Index ...
Page 401: ...376 Revision History ...