147
Setting Data Links
Section 5-2
11. If the LR Area in the C200HX/HG/HE or CQM1H-series PLC is automati-
cally set for a data link with a CVM1, CV-series PLC or CS/CJ-series PLC,
the LR words will be linked to CIO 1000 to CIO 1063 in the CVM1, CV-se-
ries or CS/CJ-series PLC. CIO 1064 to CIO 1199 cannot be linked with
C200HX/HG/HE or CQM1H-series PLCs in this way.
C200HX/HG/HE Startup Node
Set the following DM Parameter Area of the PLC of the startup node.
Settings
Cannot be directly linked
with C200HX/HG/HE words.
LR00
LR63
to
1000
1063
to
1064
1199
to
CS/CJ-series PLCs
IR words of CS/CJ-series PLCs
= (LR words of C200HX/HG/HE or
CQM1H-series PLC) + 1000
C200HX/HG/HE or
CQM1H-series PLCs
Data link mode
Set to 01 for automatic setting.
(00 is for manual setting. Other values are invalid.)
Area 1 data link start word (BCD)
Area 1 type
Number of send words per node of area 1 (BCD)
Rightmost 4 digits of data link start word of area 2 (DM area) (BCD)
Leftmost digit of data link start word of
area 2 (BCD)
First data link status word (BCD)
BCD: Set the value as binary-coded decimal.
Nodes to participate in the data links
The numbers indicate node numbers.
The value assigned indicates whether the
node is to participate in the data links.
Participate: 1
Not participate: 0
Word N
0: Always specify 0.
– : By other setting
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
15
8
7
0
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
16 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
N+1
N+2
N+3
N+4
N+5
N+6
N+7
N+8
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
N+9
–
–
0
–
0
0
0
0
0
0
0
0
0
0
N:
Level 0 = DM 6400
Level 1 = DM 6420
Area 2 type
Number of send words per node of area 2 (BCD)
00
Item
Setting range
Data link mode
Specify automatic (01).
Area 1 data link start
word
Set the word address in BCD.
IR Area: IR 000 to IR 235, IR 300 to IR 511
LR Area: LR 00 to 63
Area 1 type
Set the area for area 1 in BCD.
IR Area: 80
LR Area: 86
Area 1 not used: 00
Summary of Contents for C200HW-CLK21
Page 3: ...iv ...
Page 9: ...x ...
Page 12: ...xiii TABLE OF CONTENTS Index 367 Revision History 373 ...
Page 13: ...xiv ...
Page 19: ...xx ...
Page 57: ...32 Application Precautions Section 1 5 Example CX Programmer Response Timeout Setting ...
Page 69: ...44 Message Service Procedure Section 2 2 ...
Page 111: ...86 Constructing Networks with Repeater Units Section 3 4 ...
Page 154: ...129 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 261: ...236 Response Codes Section 6 7 ...
Page 297: ...272 Message Delay Times Section 8 4 ...
Page 353: ...328 Handling Precautions Section 9 6 ...
Page 364: ...339 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 365: ...340 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 369: ...344 Standard Models Appendix A ...
Page 391: ...366 Using the Relay Terminal Block Appendix C ...
Page 397: ...372 Index ...
Page 401: ...376 Revision History ...