CJ-series Controller Link Units
Section 4-2
5.
The default setting is “0.”
6.
The unit number determines the words used by the Controller Link Unit in
PLC memory.
4-2-3
Node Addresses
Set the node addresses of each Unit on the Network using the rotary switches
on the front of the Unit. The node address is used to identify each node in the
Network can be set to any number between 01 and 32.
Set the node address using a small flat-blade screwdriver, being careful not to
damage the rotary switches.
Note
1.
When all of the following conditions are satisfied, node addresses can be
set between 01 and 62, and the network can contain up to 62 nodes.
a) All nodes in the Controller Link network use CS1W-CLK21-V1, CS1W-
CLK23, CJ1W-CLK21-V1, or CJ1W-CLK23 Units.
b) The Wired Network 62 Node Enable Bit in the DM Parameter Area
software switches (bit 11 of 100
×
Unit No.) of all nodes is
turned ON.
c)
At least one CS1W-RPT01 Repeater Unit is connected and the num-
ber of nodes in a single segment does not exceed 31.
2.
Always turn OFF the PLC’s power before setting the node addresses.
3.
Do not set the same node address twice within the same Network. An error
will occur if the same address is set for two different nodes. The ERC indi-
cator on the front of the Unit will light (Communications Error Flag) and ei-
ther communications will stop, or the INS indicator will not light and you will
be unable to participate in the Network.
4.
When CS1W-CLK21-V1, CS1W-CLK23, CJ1W-CLK21-V1, and CJ1W-
CLK23 Units are used with other models in the same Network, set the
node addresses of all nodes between 1 and 32. In a network containing
pre-version-1 models, it is not possible to construct a network that uses a
node address higher than 32.
Turn ON the Wired Network 62 Node Enable Bit (bit 11 of 100
×
Unit No.) in the DM Parameter Area software switch of all CS1W-CLK21-
V1, CS1W-CLK23, CJ1W-CLK21-V1, and CJ1W-CLK23 Units to restrict
the network to 32 nodes maximum. If a different value is specified, the net-
work will be incorrectly configured.
5.
To construct a network that uses a node address higher than 32, it is nec-
essary for all nodes to be CS1W-CLK21-V1, CS1W-CLK23, CJ1W-
CLK21-V1, or CJ1W-CLK23 Units.
In addition, the Wired Network 62 Node Enable Bit of the DM Parameter
Area software switch of all nodes must be turned ON to enable 62 nodes
maximum. If a different value is specified, the network will not be correctly
configured.
Item
Specifications
Setting method
2-digit decimal
Setting range
01 to 32 (default is 01) (See note 1.)
Node
All nodes in the Network
NODE
No.
x10
1
x10
0
01
2 3 45
678
9
01
2 3 45
678
9
Note:
The factory default settings are shown.
Summary of Contents for C200HW-CLK21
Page 3: ...iv ...
Page 9: ...x ...
Page 12: ...xiii TABLE OF CONTENTS Index 367 Revision History 373 ...
Page 13: ...xiv ...
Page 19: ...xx ...
Page 57: ...32 Application Precautions Section 1 5 Example CX Programmer Response Timeout Setting ...
Page 69: ...44 Message Service Procedure Section 2 2 ...
Page 111: ...86 Constructing Networks with Repeater Units Section 3 4 ...
Page 154: ...129 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 261: ...236 Response Codes Section 6 7 ...
Page 297: ...272 Message Delay Times Section 8 4 ...
Page 353: ...328 Handling Precautions Section 9 6 ...
Page 364: ...339 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 365: ...340 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 369: ...344 Standard Models Appendix A ...
Page 391: ...366 Using the Relay Terminal Block Appendix C ...
Page 397: ...372 Index ...
Page 401: ...376 Revision History ...