131
Setting Data Links
Section 5-2
Data Link Tables
5-2-4
Automatic Setting
Data links can be automatically created by setting values in the DM Parameter
Area of the PLC’s CPU Unit of the startup node. The settings are made using
a Programming Console or the CX-Net in the CX-Programmer.
The startup node is the node from which the data links are activated. When
automatically setting data links, data link operation is based on the values set
in the startup node.
Note
Automatic setting appears as “Select All” on the Controller Link Support Soft-
ware message screens.
Note
Data links can be started using one of the following (See p 155.)
• Using a software switch
• Using Controller Link Support Software or CX-Net (in CX-Program-
mer)
• Using FINS commands.
Software switch
(DM area)
Startup node
CPU Unit
Or
Programming Console
CX-Net
(in CX-Programmer)
IBM PC/AT or
compatible
Controller Link
Summary of Contents for C200HW-CLK21
Page 3: ...iv ...
Page 9: ...x ...
Page 12: ...xiii TABLE OF CONTENTS Index 367 Revision History 373 ...
Page 13: ...xiv ...
Page 19: ...xx ...
Page 57: ...32 Application Precautions Section 1 5 Example CX Programmer Response Timeout Setting ...
Page 69: ...44 Message Service Procedure Section 2 2 ...
Page 111: ...86 Constructing Networks with Repeater Units Section 3 4 ...
Page 154: ...129 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 261: ...236 Response Codes Section 6 7 ...
Page 297: ...272 Message Delay Times Section 8 4 ...
Page 353: ...328 Handling Precautions Section 9 6 ...
Page 364: ...339 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 365: ...340 Changing the Data Link Tables with Active Data Links Section 10 2 ...
Page 369: ...344 Standard Models Appendix A ...
Page 391: ...366 Using the Relay Terminal Block Appendix C ...
Page 397: ...372 Index ...
Page 401: ...376 Revision History ...