39
Accessing Parameters
Section 4-5
Table 36 Input Process Area with Inverter Tripped
Note 1
Notice that the Inverter trips with an E12, the Flt bit is set and the Rdy bit
cleared.
4-4-2
Clearing a Trip
!WARNING
In the event that the Inverter trips, be sure to investigate the cause of this trip
thoroughly before clearing the trip. Not checking the cause may result in
unexpected operation. Refer to section
5-1 Troubleshooting using the LED
indicators
or section
5-2 Troubleshooting Using PROFIBUS Diagnostics
.
Step 3
You must always immediately clear the Run bit in your PLC program when a
rising edge is detected on Flt. If the Run bit is set when the trip condition is
cleared, the Inverter will immediately start running!
Step 4
Set the Rst bit in the STW register to clear the trip.
Table 37 Output Process Area when Clearing Trip
!WARNING
Always clear the Run bit (STW) in your PLC program on a rising-edge of Flt
(ZSW). Not doing so may result in the motor starting unexpectedly when the
trip is cleared via PROFIBUS or the "Stop/reset" button on the Inverter.
4-5
Accessing Parameters
4-5-1
Parameter Processing Message Area - PKW
Table 38 Input and Output Parameter Processing Message Area-PKW
I111E-EN-02+3G3AX-MX2-RX-PRT+OperManual.book Seite 39 Donnerstag, 8. September 2011 11:53 11
Summary of Contents for 3G3AX-MX2-PRT-E
Page 6: ...vi...
Page 14: ...xiv Compliance with EC Directives...
Page 20: ...6 Introduction to PROFIBUS Section 1 3...
Page 36: ...22 How to mount the Option Board on the Inverter Section 2 3...
Page 42: ...28 Configuring the Network Section 3 2...
Page 70: ...56 Limitations Caused by Inverter Mode and Rating Selection Section 4 7...
Page 108: ...94 APPENDIX G...
Page 110: ...96 APPENDIX H...
Page 113: ...97...
Page 115: ......