91
APPENDIX F
APPENDIX F
Option Board Parameters
Table F-1 Option Board Parameters
PNU R/W Res
Name
IND in
PNU
Description
Inverter
Param
890
R
-
Commissioning mode status
-
0: Commissioning mode NOT active
1: Commissioning mode active
-
W
-
Set commissioning mode
time
-
The number of seconds for commissioning mode to
remain active
-
904
R
-
PPO Write format
-
1: PPO1, 2: PPO2, 3: PPO3, 4: PPO4, 5: PPO5
-
911
R
-
PPO Read format
-
1: PPO1, 2: PPO2, 3: PPO3, 4: PPO4, 5: PPO5
-
918
R
-
PROFIBUS node address
-
The Option Board node address
P180
963
R
-
Baudrate on PROFIBUS
-
0:
9.6kbps,
1: 19.2kbps,
2: 93.75kbps,
3: 187.5kbps,
4:
500kbps,
6:
1.5Mbps,
7:
3Mbps,
8:
6Mbps,
9:
12Mbps,
10: 31.25kbps, 11: 45.45kbps
-
964
R
-
Option Board Identification
-
Array of words:
[1]: Manufacturer ID = 328,
[2]: Drive unit type = 1,
[3]: Firmware version = xxyy (Ver. xx.yy),
[4]: Firmware year = YYYY,
[5]: Firmware date = DDMM,
[6]: Number of drive Objects = 1
-
965
R
-
Profile code
-
0302h
-
967
R/W
-
STW
-
Current value of STW
-
968
R
-
ZSW
-
Current value of ZSW
-
915
R/W
-
Output PZD assignments
1
Modbus address mapped into output PZD1
0 (zero) means STW
P160
2
Modbus address mapped into output PZD2
0 (zero) means HSW
P161
3
Modbus address mapped into output PZD3
P162
4
Modbus address mapped into output PZD4
P163
5
Modbus address mapped into output PZD5
P164
6
Modbus address mapped into output PZD6
P165
7
Modbus address mapped into output PZD7
P166
8
Modbus address mapped into output PZD8
P167
9
Modbus address mapped into output PZD9
P168
10
Modbus address mapped into output PZD10
P169
916
R/W
-
Input PZD assignments
1
Modbus address mapped into input PZD1
0 (zero) means ZSW
P170
2
Modbus address mapped into input PZD2
0 (zero) means HIW
P171
3
Modbus address mapped into input PZD3
P172
4
Modbus address mapped into input PZD4
P173
5
Modbus address mapped into input PZD5
P174
6
Modbus address mapped into input PZD6
P175
7
Modbus address mapped into input PZD7
P176
8
Modbus address mapped into input PZD8
P177
9
Modbus address mapped into input PZD9
P178
10
Modbus address mapped into input PZD10
P179
I111E-EN-02+3G3AX-MX2-RX-PRT+OperManual.book Seite 91 Donnerstag, 8. September 2011 11:53 11
Summary of Contents for 3G3AX-MX2-PRT-E
Page 6: ...vi...
Page 14: ...xiv Compliance with EC Directives...
Page 20: ...6 Introduction to PROFIBUS Section 1 3...
Page 36: ...22 How to mount the Option Board on the Inverter Section 2 3...
Page 42: ...28 Configuring the Network Section 3 2...
Page 70: ...56 Limitations Caused by Inverter Mode and Rating Selection Section 4 7...
Page 108: ...94 APPENDIX G...
Page 110: ...96 APPENDIX H...
Page 113: ...97...
Page 115: ......