27
Configuring the Network
Section 3-2
Step 7
Uncheck the Enable DPV1 option on the DPV1 tab before proceeding to Step
7 if you are using OMRON CX-Configurator.
Step 8
Save and download the configuration to your PROFIBUS master.
Step 9
Once the network is re-started with the new settings, check that the Option
Board LED indicators indicate proper operation: If everything is correctly con-
figured, only the RUN and COMM indicators will be ON (green). Please refer
to section
5-1 Troubleshooting using the LED indicators
on page 57 to trouble-
shooting any configuration errors if the LED indicators are displaying a differ-
ent pattern.
Note
Nothing prevents you from selecting an unsupported module in Step 6. If you
are uncertain, check the value of P182 before selecting the module.
Tip
Refer to
SECTION 5 Troubleshooting and Maintenance
on page 57 in case of
errors.
Table 13 Configuration of module support
P182
Device Profile
Supported Modules
0
(default)
PROFIdrive
[Appendix B]
PPO Type 1 (4 words PKW + 2 words PZD)
PPO Type 2 (4 words PKW + 6 words PZD)
PPO Type 3 (2 words PZD)
PPO Type 4 (6 words PZD)
PPO Type 5 (4 words PKW + 10 words PZD)
1
Conventional
[Appendix C]
Basic Data
Extended Data 1
Extended Data 2
2
Flexible
[Appendix D]
Flexible (10 words output and input)
I111E-EN-02+3G3AX-MX2-RX-PRT+OperManual.book Seite 27 Donnerstag, 8. September 2011 11:53 11
Summary of Contents for 3G3AX-MX2-PRT-E
Page 6: ...vi...
Page 14: ...xiv Compliance with EC Directives...
Page 20: ...6 Introduction to PROFIBUS Section 1 3...
Page 36: ...22 How to mount the Option Board on the Inverter Section 2 3...
Page 42: ...28 Configuring the Network Section 3 2...
Page 70: ...56 Limitations Caused by Inverter Mode and Rating Selection Section 4 7...
Page 108: ...94 APPENDIX G...
Page 110: ...96 APPENDIX H...
Page 113: ...97...
Page 115: ......