Instruction Manual
OCM F
OCM F - Rev. 04 as of 18.02.2014
Page 77
The readings below will be indicated after the second measurement has been
finished:
−
h_actual
: actual level
−
h
: level before creating a dam-up
−
v
: measured flow velocity
−
Q
: investigated flow
Fig. 9-77 Assistant indicating investigated values
Pressing >ENTER< determines and subsequently enters an application coeffi-
cient (factor) for the measurement point.
9.6.3 CAL Menu “Analog Outputs“
Basic Hints on Simulation:
DANGER
High risk potential during simulation
Due to the extremely high risk potential (direct access to following plant sec-
tions) as well as incalculable effects due to poor or faulty simulation, NIVUS
herewith refuse to accept any responsibility for personal or material damages
of any kind in advance!
Simulations must be carried out by trained expert personnel exclusively!
Adjustment
The 3 analog outputs can be adapted to following systems. Adjust between
-4 mA and 4 mA (see Fig. 9-78).
These values will be added to or subtracted from the analog outputs. Adjust-
ment is not possible as soon as the analog output has been set to “Constant
value”.
Fig. 9-78
Adjustment of analog outputs