112
5
GROUNDING
The Drive electrical panel and Motor are individually connected to the
same ground system; the connection cables between the drive and motor
are grounded on both sides (both PE conductors and the screens of such
cables).
FERRITES
For applications in which more motors are connected to one drive and is not
possible to completely screen the cables due to a junction terminal board of
the individual motor cables, it is necessary to provide ferrite cores at the drive
output. For the correct use it is necessary to wrap the three cables (2 to 5
times) through the ferrite, leaving the grounding cable outside.
The cable that goes from the drive to the junction terminal board, without
screening, must be as short as possible.
The AD1A030-166 units have an internal ferrite core at the output.
5.9.4 MOTOR CABLES - 5.9.4.1 - 5.9.4.2