29
1/2
2
2.8 LEAKS AND VENTILATION DATA
The drives AD1000 (AD1A0P3-0P6 excluded) are provided with an internal
fan, with the flow of the incoming air positioned downward.
Table 2.8.1 Ventilation data
AD1000
Output current
Cl.1
A
3.8
21
40
9.5
12
32
65
96
5.6
25
52
16
40
77
Cl.2
A
2.1
16
32
5.6
9.5
25
52
77
3.8
21
40
12
32
65
Leaks
Cl.1
W
45
276
555
120
165
450
900
1350
66
330
660
225
555
1100
Cl.2
W
22
225
450
66
120
330
660
1100
45
276
555
165
450
900
Control
W
40
40
40
40
40
40
50
50
40
40
40
40
40
50
Ventilation
Capacity
m
3
/h
NA
100
100
NA
66
100
280
280
NA
100
100
100
100
280
ft
3
/s
NA
59
59
NA
36
59
164
164
NA
59
59
59
59
164
Fan data
Voltage
V
NA
Internal Power Supply
Internal Power Supply
NA
Internal Power Supply
Internal Power Supply
Internal Power Supply
Internal Power Supply
NA
Internal Power Supply
Internal Power Supply
Internal Power Supply
Internal Power Supply
Internal Power Supply
AD1A0P3F
AD1A015F
AD1A030F
AD1A0P6F
AD1A008F
AD1A022F
AD1A045F
AD1A066F
AD1A0P4F
AD1A018F
AD1A036F
AD1A011F
AD1A028F
AD1A053F
Current
A
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
Three-phase power supply network 400 - 480V ±10%
2.8 LEAKS AND VENTILA
TION DA
TA