5
It is necessary to use forklift trucks to transport the units in their proper
installation location. The units must be carefully lifted by the pallets up
to the final position, using a mechanical lifting device, such as a crane or
a forklift.
NOTE 1
Keep the protection packaging until the installation and start-up are
completed.
NOTE 2
For sizes AD1A210F to AD1A520F, after the drive has been installed in the
electric panel it is compulsory to remove the lifting eyebolts.
5.2 STORAGE
Following the initial inspection, the equipment must be immediately
transported into its final installation position or in a dry storage area,
protected from weather and with a controlled temperature. Although
each drive is adequately protected against environmental and weather
conditions, there are environmental conditions that can reduce its
performance, operation, and lifetime. The drive is not waterproof and
must never be stored outdoors.
The table 2.4.1 shows the rated environmental conditions.
The operator should consult the factory for doubtful matters that may
exist in particular places.
5.3 MECHANICAL INSTALLATION
5.3.1 GENERAL PRECAUTIONS
• Do not install the drive on a vibrating surface.
• The environment must be free of dust, metal particles, suspended oil,
gas and splashes of corrosive liquids.
• The drive must be installed in a vertical position.
Do not install the unit at an angle more than + 30% from the vertical axis.
• If multiple drives are installed in the same electrical panel, they
should be placed side by side. When they are installed superimposed
prevent the upper module from being affected by the hot air of the
underneath module.
NOTE
For sizes AD1A210F to AD1A520F, after the drive has been installed in the
electric panel it is compulsory to remove the lifting eyebolts.