2.5 ELECTRICAL DATA
Table 2.5.1 Electrical data - Three-phase power supply network 380V, 400V, 415V, 440V, 460V, 480V±10%
Type
AD1000 – AC 6 pulse version - 380/480Vac
Size
I
I
III
IIIX
IIIL
IIIN
IVN
VN
VIN
I
II
III
IIIX
IIIN
IVN
IVN
VN
VIN
Cl.1 – Overload: 110% for 1 min, every 10 min
1
I
N
1(*)
A
3.8
9.5
16
25
40
52
77
124
180
5.6
12
21
32
40
65
96
156
210
AD1A0P3FBBNH
AD1A0P6FBBNH
AD1A011FBBNH
AD1A018FBBNH
AD1A028FBBNH
AD1A036FBBFH
AD1A053FBNFH
AD1A086FBNFH
AD1A125FBNFH
AD1A0P4FBBNH
AD1A008FBBNH
AD1A015FBBNH
AD1A022FBBNH
AD1A030FBBFH
AD1A045FBNFH
AD1A066FBNFH
AD1A108FBNFH
AD1A150FBNFH
kW
1.5
4.0
7.5
11
18.5
22
37
55
90
2.2
5.5
9.0
15
18.5
30
45
75
110
A
3.6
8.6
15.5
22.5
37
43
69
100
160
5
11.5
18.4
30.2
37
58
84
135
195
HP
2
5
10
20
30
40
60
100
150
3
7.5
15
25
30
50
75
125
A
3.4
7.6
14
25
36
49
71
109
173
4.8
11
19.7
30.5
36
62
86
139
A
2.1
5.6
12
21
32
40
65
96
156
3.8
9.5
16
25
32
52
77
124
180
kW
0.75
2.2
5.5
9
15
18.5
30
45
75
1.5
4.0
7.5
11
15
22
37
55
90
A
2
5
11.5
18.4
30.2
37
58
84
135
3.6
8.6
15.5
22.5
30.2
43
69
100
160
HP
1.5
3
7.5
15
25
30
50
75
125
2
5
10
20
25
50
60
100
150
A
2
4.8
11
19.7
30.5
36
62
86
139
3.4
7.6
14
25
30.5
49
71
109
173
2
I
N
2(*)
motor (4p)’@400V
motor (4p)’@400V
motor (4p)’@460V
motor (4p)’@460V
Cl.2 - Overload: 150% for 1min, every 10 min
2.5 ELECTRICAL DA
TA
PREVIOUS VIEW
BACK 1.2
Summary of Contents for AD1A008FBBNH
Page 138: ......