4.3.3 REQUIREMENTS IN CASE OF MAINTENANCE
SAFETY REQUIREMENT
All maintenance and installation operations on the AD1000 must be
performed by qualified technical personnel. Nidec ASI S.p.A. is not
responsible for damage due to improper or unauthorized maintenance.
DANGER! RISK OF DEATH OR ELECTRIC SHOCK! It is necessary to take the
following compulsory measures before the maintenance of this unit:
• Perform the power supply locking/disabling procedure and open
the main disconnector on the electrical panel that contains the AD1000.
• Make sure that all power supplies that come to the drive
(main power supply, auxiliary power supply) are disconnected before
performing maintenance on the drive
• Before performing any maintenance on the machine wait 10 minutes
after disconnecting all power sources and ensure that the DC voltage is
less than 50V. Use a 1000 V DC multimeter or higher. Refer to the safety
label placed on each drive.
4.3.3 REQUIREMENTS IN CASE OF MAINTENANCE