Answer Drives 1000
30
2/2
2
Table 2.8.1 Ventilation data
AD1000
Output current
Cl.1
A
210
410
690
156
300
540
124
240
510
750
180
370
640
Cl.2
A
180
320
530
124
240
410
96
200
385
585
156
285
510
Leaks
Cl.1
W
3300
4350
7450
2250
3350
5800
1650
3300
5500
7900
2700
4000
6600
Cl.2
W
2700
3250
5500
1650
2550
4150
1350
2700
3950
5850
2250
2900
5100
Control
W
80
90
100
60
90
100
60
80
100
100
60
90
100
Ventilation
Capacity
m
3
/h
500
800
1400
280
800
1400
280
500
1400
1400
500
800
1400
ft
3
/s
293
16
471
824
471
824
164
293
824
824
293
471
824
Fan data
Voltage
V
230V 50/60Hz
Internal Power Supply
230V 50/60Hz
230V 50/60Hz
230V 50/60Hz
230V 50/60Hz
Internal Power Supply
230V 50/60Hz
230V 50/60Hz
230V 50/60Hz
230V 50/60Hz
230V 50/60Hz
230V 50/60Hz
AD1A150F
AD1A290F
AD1A480F
AD1A108F
AD1A210F
AD1A370F
AD1A086F
AD1A166F
AD1A350F
AD1A520F
AD1A125F
AD1A260F
AD1A440F
Current
A
0,9
NA
1,2
2,2
1,2
2,2
NA
0,9
2,2
2,2
0,9
1,2
2,2
Three-phase power supply network 400 - 480V ±10%
2.8 LEAKS AND VENTILA
TION DA
TA
• The Fans of the AD1000 are designed exclusively to meet the losses
of the drive. For installation in a panel, it is necessary to consider also
the additional loss of pressure.
• AD1A125F and superior. The user must provide a protection device
for the fan.