BIT
#
VALUE DEFINITION
0
0
disable E-stop checking
*0
1
enable E-stop checking
*1
0
do not disable motor power on E-stop event
1
1
disable motor power on E-stop event
2
0
do not abort motion on E-stop event
*2
1
abort motion on E-stop event
3 0
reserved
3 1
reserved
4 0
reserved
4 1
reserved
5 0
reserved
5 1
reserved
6 0
reserved
6 1
reserved
7 0
reserved
7 1
reserved
•
•
•
31 0
reserved
31 1
reserved
* default setting
RETURNS
If the “?” sign takes the place of
nn
value, this command reports the current
setting in hexadecimal notation.
REL. COMMANDS
ZA
-
set amplifier I/O configuration
ZB -
set feedback configuration
ZF -
set following error configuration
ZH -
set hardware limit configuration
ZS -
set software limit configuration
ZZ -
set general system configuration
EXAMPLE
2ZE?
|
read e-stop configuration of axis # 2
3H
|
controller returns a
value of 3H for axis #2
2ZE 5H
|
set e-stop configuration to 5H for axis #2
SM
|
save all controller settings to non-volatile memory
3-164
Section
3
–
Remote
Mode
Summary of Contents for ESP300 Series
Page 1: ...ESP300 Motion Controller Driver User s Manual...
Page 4: ...ESP300 1999 EU Declaration of Conformity iv Preface...
Page 29: ...This page is intentionally left blank Section 2 Modes of Operation 1 15...
Page 30: ......
Page 230: ...4 16 Section 4 Advanced Capabilities...
Page 274: ...This page is intentionally left blank 6 6 Section 6 Servo Tuning...
Page 290: ...This page is intentionally left blank B 6 Appendix B Trouble Shooting and Maintenance...