LP
list program
IMM
PGM
MIP
USAGE
♦
♦
SYNTAX
xx
LP
Units
xx
-
none
PARAMETERS
Description
xx
[ int ] -
program number
Range
xx
-
1
to
100
Defaults
xx
missing:
error 38, COMMAND PARAMETER MISSING
out of range: error 7, PARAMETER OUT OF RANGE
DESCRIPTION
This command reads a specified program from non-volatile memory and sends it
to the selected communication port (RS232 or IEEE488). During the
transmission no other command should be sent to the controller.
Note:
The program list always terminates with the word “END”
.
RETURNS
program listing
REL. COMMANDS
EP
-
enter program mode
EXAMPLE
3LP
|
list program number 3
3MO
|
enable
axis
3
motor
power
1DL
|
define
return
label
1
3PR+10
| move axis 3 re10 units
3WS500
| wait 500ms after axis 3 stops
3PR-10
| move axis 3 relative -10 units
3WS500
| wait 500ms after axis 3 stops
1JL5
| jump to label 1 location 5 times
END
|
end
of
program
list