WP
wait for position
IMM PGM MIP
Range
xx
-
1
to
MAX AXES
nn
missing:
error 38, COMMAND PARAMETER MISSING
Note:
RETURNS
None
USAGE
♦
♦
♦
SYNTAX
xx
WP
nn
PARAMETERS
Description
xx
[ int ]
-
axis number
nn
[ float ] -
position value
nn
-
starting position to destination of axis number
xx
Units
xx
-
none
nn
-
predefined
units
Defaults xx
missing:
error 37, AXIS NUMBER MISSING
out of range:
error 9, AXIS NUMBER OUT OF RANGE
out of range:
error 7, PARAMETER OUT OF RANGE
DESCRIPTION
This command stops program execution until a user specified position is reached.
The program continues executing any subsequent commands only after axis
xx
has reached position
nn
.
Ensure that position
nn
is within the travel range of axis
xx
. The controller
cannot always detect if a value is outside the travel range of an axis to flag an
error, especially while making coordinated motion of multiple axes.
Wait commands are primarily intended for use in internal program execution or
in combination with the RQ command. If used in command mode, it is important
to note that input command processing is suspended until the wait condition has
been satisfied.
REL. COMMANDS
WT
-
wait
WS
-
wait for motion stop
EXAMPLE
2PA-10; 2WS
|
move axis # 2 to position –10 units and wait for stop
2PA10;
2WP0
; 3PA5 |
move axis #2 to position 10 units, wait for axis #2 to
reach
position 0 units and then move axis #3 to position
5 units
Section 3 – Remote Mode
3-153
Summary of Contents for ESP300 Series
Page 1: ...ESP300 Motion Controller Driver User s Manual...
Page 4: ...ESP300 1999 EU Declaration of Conformity iv Preface...
Page 29: ...This page is intentionally left blank Section 2 Modes of Operation 1 15...
Page 30: ......
Page 230: ...4 16 Section 4 Advanced Capabilities...
Page 274: ...This page is intentionally left blank 6 6 Section 6 Servo Tuning...
Page 290: ...This page is intentionally left blank B 6 Appendix B Trouble Shooting and Maintenance...