To set the primary transformer current, proceed as follows:
1.
Go to
Settings > Parameters > Transformer data > Primary trans-
former current
.
2.
Enter primary transformer current.
3.
Press the
Accept
button to save the modified parameter.
Setting the secondary transformer current
You can use this parameter to set the secondary transformer current. You
can select the following options:
▪
0.2 A
▪
1 A
▪
5 A
To set the secondary transformer current, proceed as follows:
1.
Go to
Settings > Parameters > Transformer data > Secondary trans-
former current
.
2.
Select secondary transformer current.
3.
Press the
Accept
button to save the modified parameter.
Setting circuit for current transformer/voltage transformer and
phase angle correction
To configure the circuit for the current transformer and voltage transformer,
you must set the following parameters:
Parameter
Measuring module
UI 1
UI 3
Voltage-transformer circuit
Yes
Only with 1
channel
Current-transformer circuit
Yes
Only with 1
channel
Phase angle correction
Yes
Only with 1
channel
UI measuring channels
No
Yes
Measurement mode
No
Only with 3
channels
Table 13: Setting configuration of current transformer and voltage transformer
Note the following examples of common transformer circuits: