6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
165
5163667/00 EN
TRAFOGUARD® ISM®
Be sure to enter a valid network mask that is not 0.0.0.0, otherwise it will not
be possible to connect to the device.
To set the subnet mask, proceed as follows:
1.
Go to
Settings > Parameters > IEC
60870-5-104 > Subnet mask
.
2.
Enter subnet mask.
3.
Press the
Accept
button to save the modified parameter.
Gateway address
You can use this parameter to set the gateway's IP address.
If you set the value to 0.0.0.0, no gateway is used.
To set the gateway address, proceed as follows:
1.
Go to
Settings > Parameters > IEC
60870-5-104 > Gateway address
.
2.
Enter gateway address.
3.
Press the
Accept
button to save the modified parameter.
TCP port
You can use this parameter to set the TCP port.
To set the TCP port, proceed as follows:
1.
Go to
Settings > Parameters > IEC
60870-5-104 > TCP port
.
2.
Enter TCP port.
3.
Press the
Accept
button to save the modified parameter.
ASDU address
You can use this parameter to set the address of the ASDU.
To set the ASDU address, proceed as follows:
1.
Go to
Settings > Parameters > IEC
60870-5-104 > ASDU address
.
2.
Set ASDU address.
3.
Press the
Accept
button to save the modified parameter.