6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
164
5163667/00 EN
TRAFOGUARD® ISM®
Number of stop bits
You can use this parameter to set the number of stop bits.
To set the number of stop bits, proceed as follows:
1.
Go to
Settings > Parameters > IEC
60870-5-103 > Number of stop
bits
.
2.
Set number of stop bits.
3.
Press the
Accept
button to save the modified parameter.
Configuring IEC 60870-5-104 (optional)
If you want to use the IEC 60870-5-104 control system protocol, you must
set the following parameters.
Figure 124: Setting parameters for IEC60870-5-104
IP address
You can use this parameter to assign an IP address to the device.
To set the IP address, proceed as follows:
Assign IP addresses to both web-based visualization and SCADA (optional)
in different subnets. Otherwise you will not be able to establish a connec-
tion.
1.
Go to
Settings > Parameters > IEC
60870-5-104 > IP address
.
2.
Enter IP address.
3.
Press the
Accept
button to save the modified parameter.
Subnet mask
You can use this parameter to set the subnet mask.
6.22.4