10 Technical data
Maschinenfabrik Reinhausen GmbH 2016
213
5163667/00 EN
TRAFOGUARD® ISM®
CAN bus
Terminating resistor
▪
D-SUB plug connector (9 pins)
▪
R = 120 Ω
Connector with terminal strip for directly con-
necting CAN lines
Media converter for
COM2 interface (only
RS232)
Adapter from D-SUB (9 pins) to fiber-optic ca-
ble:
▪
ACF660/ST: F-ST, 660 nm, range max. 60
m at 40 kilobaud
▪
ACF660/SMA: F-SMA, 660 nm, range max.
60 m at 40 kilobaud
▪
ACF850/ST: F-ST, 850 nm, range max.
1000 m at 40 kilobaud
▪
ACF850/SMA: F-SMA, 850 nm, range max.
1000 m at 40 kilobaud
Table 65: Optional accessories
System networking
MC 2-2
Description
Media converter
Interfaces
2x RJ45
2x duplex LC (SFP)
RJ45
Max. 100 m (per section)
10/100 Mbit/s
Cable impedance 100 Ω
Fiber-optic cable
Max. 2,000 m
100 Mbit/s
1,310 nm
Table 66: Technical data for the MC 2-2 assembly
SW 3-3
Description
Managed Fast Ethernet Switch in accord-
ance with IEEE 802.3, store-and-forward-
switching
Interfaces
2x RJ45
2x duplex LC (SFP)
Redundancy protocols
Time synchronization
PTPv2 (IEEE 1588-2008)
10.7
Summary of Contents for TRAFOGUARD ISM
Page 1: ...Monitoring System TRAFOGUARD ISM Operating Instructions 5163667 00 EN ...
Page 222: ......