6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
84
5163667/00 EN
TRAFOGUARD® ISM®
Active power-dependent adjustment of desired voltage value with 3
different desired values
The TAPCON® Dynamic Setpoint Control (TDSC) function is used to adapt
the desired voltage value depending on the measured active power. This al-
lows you to compensate for a voltage drop during increased load or an in-
crease in voltage due to a decentralized feed-in.
The device provides you with 3 different sets of parameters for this purpose.
Depending on the selection of the desired value 1, 2 or 3, the device uses
the parameter set 1, 2 or 3 for TDSC.
Depending on whether positive or negative active power is measured, the
desired value calculation is based on 2 linear equations (see example in dia-
gram below).
Parameter
Function
Settings (see dia-
gram below)
U
max
: Maximum desired value
Maximum set desired value is activated when
P
max
is exceeded.
103.0 V
U
min
: Minimum desired value
Minimum set desired value is activated when
value falls below P
min
.
99.0 V
U
0
: Desired value at 0 active
power
Set desired value is activated when measured
active power is 0 MW.
100.00 V
P
max
: Active power at max.
desired value
Set maximum active power value above which
the power-dependent desired value is to attain
the maximum value U
max
.
20.0 MW
P
min
: Active power at min. de-
sired value
Set minimum active power value below which
the power-dependent desired value is to attain
the minimum value U
min
.
-20.0 MW
Table 11: Parameters to be set for active power-dependent adjustment of desired voltage value