5 Commissioning
Maschinenfabrik Reinhausen GmbH 2016
65
5163667/00 EN
TRAFOGUARD® ISM®
Figure 62: Perform a ground test on the DIO assembly (sample representation of the
DIO 28-15 assembly).
2.
Feed the test current at the grounding terminal of the G1 PULS DIMEN-
SION QS3.241 assembly using a constant current source and measure
the voltage between the measurement point and the protective conduc-
tor.
ð
The measured voltage must remain less than 10 V over a duration of 1
minute.