5 Commissioning
Maschinenfabrik Reinhausen GmbH 2016
66
5163667/00 EN
TRAFOGUARD® ISM®
Figure 63: Perform a ground test on the G1 PULS DIMENSION QS3.241 assembly
Performing a high voltage test
The device is tested before delivery Note the following points if you want to
perform a high voltage test:
NOTICE
Damage to the device during the high voltage test
A high voltage test with a test voltage that is greater than the maximum per-
mitted test voltage can lead to damage to the device.
► Perform the high voltage test with a test voltage that is less than or
equal to the maximum permitted test voltage.
► Perform the high voltage test using only the permitted interfaces.
Based on the device configuration, you must only test the following assem-
blies. You must not test any other assemblies.
Assembly
Interfaces
Test parameters
max. test volt-
age
max. test du-
ration
Ramp
Breaking cur-
rent threshold
OT1205
(MR/N)
1
N, L
2.2 kV AC
2 s
5 s
> 10 mA
UI 1
N, L
k, l
> 4 mA
UI 3
N, L1, L2, L3
k1, l1, k2, l2,
k3, l3
> 4 mA
5.1.2