6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
120
5163667/00 EN
TRAFOGUARD® ISM®
If the value falls below or exceeds the set bandwidth [
Function
monitoring
event is displayed after the set delay time for function monitoring
has elapsed. The event is automatically acknowledged as soon as the
measured value returns to within the set bandwidth.
The following parameters are available for setting function monitoring:
▪
Function monitoring
▪
Hysteresis
▪
Delay time
Figure 86: Setting function monitoring
Activating function monitoring
You can use this parameter to activate function monitoring. You can select
the following options:
Setting
Behavior
Off
Function monitoring is deactivated.
Only Auto
Function monitoring is only active in AVR AUTO
operating mode.
Auto and Manual
Function monitoring is active in AVR AUTO and
AVR MANUAL operating mode
Table 30: Activate function monitoring
To activate function monitoring, proceed as follows:
1.
Go to
Settings > Parameters > Bandwidth monitoring > Function
monitoring
.
2.
Select the option you want from the list box.
3.
Press the
Accept
button to save the modified parameter.
Behavior
Summary of Contents for TRAFOGUARD ISM
Page 1: ...Monitoring System TRAFOGUARD ISM Operating Instructions 5163667 00 EN ...
Page 222: ......
Page 223: ......