12 Overview of parameters
Maschinenfabrik Reinhausen 2014
155
222/08 EN
TAPCON® 240
Parameter
Setting range
Factory setting
Current setting
U< Delay
0...20 s
10.0 s
U< also under 30 V
On/Off
Off
U> Overvoltage (%)
100...140 %
110.0 %
U> Overvoltage (V)
34...160 V
110.0 V
Time slice for steps
0...1800 s
0 s
Parameter > Compensation
Ur line drop comp.
-25...25 V
0.0 V
Ux line drop comp.
-25...25 V
0.0 V
Z comp. limit value
0...15 %
0.0 %
Z compensation
0...15 %
0.0 %
Parameter > Cross-monitoring
Error message
0...10 s
10 s
U prim. regulator 2
0...9999 kV
0 kV
U sec. regulator 2
57...125 V
100.0 V
U< regulator 2
34...160 V
60.0 V
U< regulator 2
60...100 %
60 %
U> regulator 2
34...160 V
140.0 V
U> regulator 2
100...140 %
140 %
U ref for regulator 2
49...140 V
100.0 V
Configuration > Transformer data
Primary voltage
0...9999 kV
0 kV
Primary current
0...9999 A
0 A
Secondary voltage
57...125 V
100.0 V
Current transformer connec-
tion
Unknown; 0.2 A; 1 A;
5 A
Unknown
Transformer circuit
0 1PH
Configuration > General
Display %/ A
On/Off
Off
Display dark
On/Off
On
Display kV / V
kV/V
V
COM1 setting
9.6 kilobaud; 19.2 kilo-
baud; 38.4 kilobaud;
57.6 kilobaud
57.6 kilobaud
R/L pulse duration
0...10 s
1.5 s
IO1-X1:23/24
Desired value 3
IO1-X1:25/26
Desired value 2
IO1-X1:31
Off
IO1-X1:33
Off
Motor runtime
0...30 s
0.0 s
Regulator ID
-
0000
Language
English
Summary of Contents for tapcon 240