7 Functions and settings
Maschinenfabrik Reinhausen 2014
120
222/08 EN
TAPCON® 240
Event lasting less than 5 minutes
If the event lasts less than 5 minutes, it is recorded in high resolution
. The
high-resolution data are first recorded 10 seconds
before the event
. If
the voltage has returned to the bandwidth
, the event is still recorded until
the overrun time of 10 seconds
has passed.
At a low resolution
, the entire process is saved.
Figure 76: Event duration (more than 5 minutes)
1
Saving at high resolution
B
Event occurs (voltage departs
from bandwidth)
2
Saving at low resolution
C
Event occurs (voltage returns
to bandwidth)
3
Run-in time/overrun time; du-
ration: 10 seconds
D
End of event's overrun time
A
Start of event's run-in time
Event lasting more than 5 minutes
The high-resolution
data are first recorded 10 seconds
before the
event
. If the event is still active after 5 minutes
, the data continues to
be saved at a low resolution
. If the voltage returns to the bandwidth
,
this is considered a new event. The high-resolution recording of new data
commences at the start of the 10-second run-in time
and ends after the
10-second overrun time
.