![MR tapcon 240 Operating Instructions Manual Download Page 103](http://html.mh-extra.com/html/mr/tapcon-240/tapcon-240_operating-instructions-manual_1844358103.webp)
7 Functions and settings
Maschinenfabrik Reinhausen 2014
103
222/08 EN
TAPCON® 240
Circuit D
TAPCON® 240
Figure 62: Phase difference 90 3PH
▪
The voltage transformer VT is connected to the outer conductors L1 and
L2.
▪
The current transformer CT is looped into the outer conductor L3.
▪
The current I
L3
is ahead of voltage U
L1
-V
L2
by 90°.
▪
The voltage drop on an outer conductor is determined by the current I
L3
.
Circuit E
TAPCON® 240
Figure 63: Phase difference 30 3PH
▪
The voltage transformer VT is connected to the outer conductors L1 and
L2.
▪
The current transformer CT is looped into the outer conductor L2.
▪
The current I
L2
is ahead of voltage U
L2
-U
L1
by 30°.
▪
The voltage drop on an outer conductor is determined by the current I
L2
.