![MR tapcon 240 Operating Instructions Manual Download Page 121](http://html.mh-extra.com/html/mr/tapcon-240/tapcon-240_operating-instructions-manual_1844358121.webp)
7 Functions and settings
Maschinenfabrik Reinhausen 2014
121
222/08 EN
TAPCON® 240
Figure 77: Event duration (more than 5 minutes)
1
High-resolution recording
B
Event occurs (voltage departs
from bandwidth)
2
Low-resolution recording
C
End of high-resolution record-
ing; start of low-resolution re-
cording
3
Duration: 10 seconds
D
Start of event's run-in time
4
Duration of high-resolution re-
cording: 5 minutes
E
Event occurs (voltage returns
to bandwidth)
A
Start of event's run-in time
F
End of event's overrun time
The table below shows the memory time. Depending on the average value
interval and the size of the event memory, it is a maximum of 401 days.
Average value
interval
Size of event memory
256 kB
512 kB
1024 kB
2048 kB
1 s
10 d
9 d
8 d
7 d
2 s
20 d
19 d
17 d
14 d
4 s
40 d
38 d
35 d
29 d
10 s
100 d
96 d
89 d
73 d
20 s
201 d
193 d
178 d
147 d
40 s
401 d
386 d
356 d
295 d
Table 31: Memory time of measured value memory