![MR tapcon 240 Operating Instructions Manual Download Page 162](http://html.mh-extra.com/html/mr/tapcon-240/tapcon-240_operating-instructions-manual_1844358162.webp)
13 Technical data
Maschinenfabrik Reinhausen 2014
162
222/08 EN
TAPCON® 240
Figure 109: Maximum contact loadability of outputs with direct current
1
Ohmic load
Analog inputs and outputs
AD
AD8
AN
Channels
2 inputs
8 inputs
2 outputs or 4
outputs (AN +
AN1)
Input signals
(depending on
configuration)
0...±20mA
0...±10mA
0...±10V
50...2000 ohms
4...20 mA
-
Output signals
(depending on
configuration)
-
-
0...±20mA
0...±10mA
0...±1mA
0...±10V
Table 54: Analog inputs and outputs (optional)
Control voltage supply (optional)
AC-115
AC-230
Input
115 V AC, 50/60 Hz
230 V AC, 50/60 Hz
Output
60 V DC
max. 0.2 A
13.5
13.6