6 Commissioning
Maschinenfabrik Reinhausen 2014
47
222/08 EN
TAPCON® 240
2.
Set overvoltage U> [%] to 115 % [
3.
Set the absolute limit values parameter to Off [
4.
Measured voltage = 100 V
Desired value 1 = Set to 85 V (less than 100 V/1.15 = 87 V).
ð
The
Overvoltage U>
LED will light up.
ð
The
Overvoltage
message appears in the display and the relevant
signaling relay is activated.
5.
Press
to select auto mode.
ð
The LOWER output relay emits a control command every 1.5 sec-
onds.
6.
Press
to select manual mode.
7.
Reset the operating values for
desired value 1
and
overvoltage U>
[%]
to the desired operating values.
ð
The function test for overvoltage blocking is complete.
Checking desired value 2 and desired value 3
1.
Press
to select manual mode.
2.
Set
desired value 2
3.
Apply voltage
L+
to terminal
desired value 2
(see connection diagram).
4.
Press
until the main screen is displayed.
ð
Desired value 2
is shown on the main screen.
5.
Set desired value 3 to the value you want [
6.
Apply voltage
L+
to terminal
desired value 3
(see connection diagram).
7.
Press
until the main screen is displayed.
ð
Desired value 3
is shown on the main screen.
ð
The function test for
desired value 2
and
desired value 3
is complete.
Checking line drop compensation
If you want to use line drop compensation, you need to run this function test.
A load current of ≥ 10 % of the nominal transformer current is needed for the
following function tests. Before the function test, ensure that all parameters
for line drop compensation [
to
0
.
1.
Press
to select manual mode.
2.
Press
until the main screen is displayed.