7 Functions and settings
Maschinenfabrik Reinhausen 2014
133
222/08 EN
TAPCON® 240
1.
>
Configuration >
Continue >
Continue >
Comm. Interface 1 > Press
until the desired display appears.
ð
SCADA Master Address CIC1.
2.
Press
to change the first digit.
If you wish to enter a multi-digit sequence, proceed to step 3. If you do not
wish to enter additional digits, proceed to step 7.
3.
Press
until another digit position appears.
4.
Press
to highlight a digit position.
ð
The required digit is highlighted and can be changed.
5.
Press
or
to change the digit.
6.
Repeat steps 3 to 5 until all required digits have been entered.
7.
Press
.
ð
The SCADA master address is set.
Enabling unsolicited messages
When using the control system protocol DNP3, you can release the unsolicit-
ed data transmission through the device with this parameter. Data is trans-
ferred when a corresponding event occurs.
This display is only provided for the following interface protocol:
▪
DNP3
The voltage regulator must be restarted after changing this setting.
To enable unsolicited messages, proceed as follows:
1.
>
Configuration >
Continue >
Continue >
Comm. interface 1 > Press
until the desired parameter is displayed.
ð
Unsolicited messages CIC1.
2.
Press
or
to set the option you want.
3.
Press
.
ð
Unsolicited messages are enabled/blocked.
7.14.9