9 Fault elimination
Maschinenfabrik Reinhausen 2014
147
222/08 EN
TAPCON® 240
Man-machine interface
Characteristics/detail
Cause
Remedy
Keys
▪
MANUAL/AUTO operat-
ing mode cannot be
changed
REMOTE operating mode
active and LED in key
il-
luminated.
Press
to activate LOCAL mode.
Keys
▪
LEDs in keys
and
not illuminated.
Parameter error
Reset parameters to factory settings
[
Display
▪
No display.
Contrast incorrectly set.
Voltage supply interrupted.
Check voltage supply.
Fuse faulty.
Contact Maschinenfabrik Reinhausen.
LEDs
▪
Freely configurable LED
lights up
Customized LED parameteri-
zation.
Check parameters.
LEDs
▪
LED flashing
Input signal not constant.
Check input signal.
COM1
▪
Cannot be connected to
PC using TAPCON®-
trol.
Different baud rates set.
Check baud rate set on device and PC.
Table 38: Man-machine interface
Incorrect measured values
Characteristics/detail
Cause
Remedy
Measured voltage
▪
No measured value.
Connection has no contact in
the plug terminal.
Check wiring and plug terminal.
Insulation trapped
Wire not inserted far enough.
Circuit breaker tripped.
Check fuse.
Measured voltage
▪
Measured value too low.
Voltage drop on measuring
lead.
Check measured voltage at plug terminal
MI:01/MI:02.
Measured voltage
▪
Measured value fluctu-
ates.
Possible sources of fault:
▪
Leads laid in parallel.
▪
Tap-change operations.
Check measured voltage at plug terminal
MI:01/MI:02.
Increase distance from source of interfer-
ence.
Install filter if necessary.
Measured current
▪
No measured value.
Line to current transformer
interrupted.
Check wiring.
Short-circuiting jumper in
current transformer not re-
moved.
Remove short-circuiting jumper.