![MR tapcon 240 Operating Instructions Manual Download Page 37](http://html.mh-extra.com/html/mr/tapcon-240/tapcon-240_operating-instructions-manual_1844358037.webp)
5 Mounting
Maschinenfabrik Reinhausen 2014
37
222/08 EN
TAPCON® 240
Figure 23: Recommended connection of the shielding
1
Connection of the shielding
using a "pigtail"
2
Shielding connection covering
all areas
Wiring requirement in control cabinet
Note the following when wiring the control cabinet:
▪
The control cabinet where the device will be installed must be prepared
in accordance with EMC requirements:
–
Functional division of control cabinet (physical separation)
–
Constant potential equalization (all metal parts are joined)
–
Line routing in accordance with EMC requirements (separation of
lines which cause interference and those susceptible to interfer-
ence)
–
Optimum shielding (metal housing)
–
Overvoltage protection (lightning protection)
–
Collective grounding (main grounding rail)
–
Cable bushings in accordance with EMC requirements
–
Any contactor coils present must be interconnected
▪
The device's connection cables must be laid in close contact with the
grounded metal housing or in metallic cable ducts with a ground con-
nection.
▪
Signal lines and power lines/switching lines must be laid in separate ca-
ble ducts.
▪
The device must be grounded at the screw provided, the protective
grounding connection, using a ground strap (cross-section min. 8 mm²).
5.3.3.3
Summary of Contents for tapcon 240
Page 1: ...Voltage Regulator TAPCON 240 Operating Instructions 222 08 EN ...
Page 173: ......