6 Commissioning
Maschinenfabrik Reinhausen 2014
52
222/08 EN
TAPCON® 240
3.
Compare the tap position displays
of devices
/
. All devices must
display the same tap position; if not, switch them into the same one.
Figure 29: Comparing tap positions
1
Master
3
Tap position display
2
Follower
To perform the function test, proceed as follows:
1.
Press
on the follower to select manual mode.
2.
If necessary, set the follower tapping direction [
3.
Press
on the master to select manual mode.
4.
Press
or
on the master to manually change the tap position.
5.
Press
on the follower to select auto mode.
ð
The follower follows the master's control command.
6.
Press
on the master to select auto mode.
7.
Press
on the follower to select manual mode.
8.
Press
or
on the follower to manually change the tap position.
ð
After expiry of the set delay time for parallel operation errors
[
Tap difference to follower
error message is displayed
in the main screen on the master.